Digital Monitoring Products XR100 Series Programming Guide
56
Zone InformatIon
18.22
FAST RSP NO YES
Fast Response
SelectYEStoprovideazoneresponsetimeof167ms.SelectNOtoprovidea
normalzoneresponsetimeof500ms.Zones500to599haveaxedresponsetime
and do not display this option.
18.23
CRS ZONE NO YES
Cross Zone
SelectYEStoenablecrosszoningforthiszone.Crosszoningrequiresoneormorearmed
zones to fault within a programmed time before an alarm report is sent to the receiver.
Whentherstcrosszonedzonetrips,thecrosszonetimespeciedinSystem
Optionsbeginstocountdown.Whenasecondcrosszonedzonetripsortherst
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
Note: For UL Installations, Cross Zoned zones must protect the same area.
18.24
PRIORITY NO YES
Priority
SelectYEStoprovideadditionalprotectionforthepremisesbyrequiringthiszone
to be in a normal condition before its assigned area can be armed.
18.25 Fire Panel Slave Input
ThisoptionisavailableonFireZones(FI)onlyandallowsarezonetheabilityto
provideslavecommunicationoperationforaseparaterealarmcontrolpanel.If
YES,thiszonewilltransmitarestoralimmediatelywhenrestoredbytherepanel
being monitored. A sensor reset is not required to generate the restoral message.
IfNO,thiszonewilloperateasastandardretypezoneandasensorresetis
required before the zone will return to normal. Default is NO.
18.26 Area Follower
AllowsNight,Day,Aux1,orAux2burglaryzonestobedelayedbyfollowinganyexit
orentrydelaythatiscurrentlyrunningintheareathatisspecied.Defaultis0.
18.27 Zone Real-Time Status
SelectingYESallowsReal-TimeStatusreports,suchasDoorOpenorClosedwith
zonenumber,tobesentusingPCLogreporting.SelectingNOdisablesReal-Time
Status for this zone. Default is NO.
18.28
ZONE AUDIT DAYS:
Zone Audit Days
Enterthenumberofdays(0to365)allowedtoelapsewithoutthezonebeingtripped
beforeafaultmessageissent.Themessageissenttothereceiver(s)programmed
toreceiveSupervisory/TroubleReportsat10:00amfollowingtheexpirationofthe
timer.Eachtimethezoneistripped,theZoneAuditDaystimerrestartsandbegins
to countdown the number of days programmed. After the countdown expires, a fault
messageissentandtheZoneAuditDaystimerrestartsandbeginstocountdownthe
numberofdaysprogrammed.Availableforallzonetypesexceptreandreverify.
Enter0(zero)todisablethisfunction.Defaultis0(zero).
18.29 Report with Account Number for Area
Thisoptionisonlyavailablefor24-hourzonetypes(Fire,FireVerify,Panic,
Emergency,orSupervisory).
Entertheareanumber(1-32)toassignasa24-hourzonetype.Thisoption
sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communicationsectionissent.Select0(zero)tohavethereportsentwiththe
account number programmed in Communication. Default is 0
FIRE PANEL SLAVE
INPUT: NO YES
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS
NO YES
0
REPORT WITH ACCT
NO. FOR AREA: 0