Digital Monitoring Products XR100 Series Programming Guide
56
Zone InformatIon
18.22
FAST RSP NO YES
Fast Response
SelectYEStoprovideazoneresponsetimeof167ms.SelectNOtoprovidea
normalzoneresponsetimeof500ms.Zones500to599haveaxedresponsetime
and do not display this option.
18.23
CRS ZONE NO YES
Cross Zone
SelectYEStoenablecrosszoningforthiszone.Crosszoningrequiresoneormorearmed
zones to fault within a programmed time before an alarm report is sent to the receiver.
Whentherstcrosszonedzonetrips,thecrosszonetimespeciedinSystem
Optionsbeginstocountdown.Whenasecondcrosszonedzonetripsortherst
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
Note: For UL Installations, Cross Zoned zones must protect the same area.
18.24
PRIORITY NO YES
Priority
SelectYEStoprovideadditionalprotectionforthepremisesbyrequiringthiszone
to be in a normal condition before its assigned area can be armed.
18.25 Fire Panel Slave Input
ThisoptionisavailableonFireZones(FI)onlyandallowsarezonetheabilityto
provideslavecommunicationoperationforaseparaterealarmcontrolpanel.If
YES,thiszonewilltransmitarestoralimmediatelywhenrestoredbytherepanel
being monitored. A sensor reset is not required to generate the restoral message.
IfNO,thiszonewilloperateasastandardretypezoneandasensorresetis
required before the zone will return to normal. Default is NO.
18.26 Area Follower
AllowsNight,Day,Aux1,orAux2burglaryzonestobedelayedbyfollowinganyexit
orentrydelaythatiscurrentlyrunningintheareathatisspecied.Defaultis0.
18.27 Zone Real-Time Status
SelectingYESallowsReal-TimeStatusreports,suchasDoorOpenorClosedwith
zonenumber,tobesentusingPCLogreporting.SelectingNOdisablesReal-Time
Status for this zone. Default is NO.
18.28
ZONE AUDIT DAYS:
Zone Audit Days
Enterthenumberofdays(0to365)allowedtoelapsewithoutthezonebeingtripped
beforeafaultmessageissent.Themessageissenttothereceiver(s)programmed
toreceiveSupervisory/TroubleReportsat10:00amfollowingtheexpirationofthe
timer.Eachtimethezoneistripped,theZoneAuditDaystimerrestartsandbegins
to countdown the number of days programmed. After the countdown expires, a fault
messageissentandtheZoneAuditDaystimerrestartsandbeginstocountdownthe
numberofdaysprogrammed.Availableforallzonetypesexceptreandreverify.
Enter0(zero)todisablethisfunction.Defaultis0(zero).
18.29 Report with Account Number for Area
Thisoptionisonlyavailablefor24-hourzonetypes(Fire,FireVerify,Panic,
Emergency,orSupervisory).
Entertheareanumber(1-32)toassignasa24-hourzonetype.Thisoption
sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communicationsectionissent.Select0(zero)tohavethereportsentwiththe
account number programmed in Communication. Default is 0
FIRE PANEL SLAVE
INPUT: NO YES
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS
NO YES
0
REPORT WITH ACCT
NO. FOR AREA: 0