Digital Monitoring Products XR100 Series Programming Guide
18
Device Setup
•DoorOn/OffMenuoperationisallowedfordevicesthathaveamatchingarea(s)
asdenedinDeviceAccessAreas
Note:Theprevioususeractionsalsorequirethematchingarea(s)beprogrammed
inUserProle:Arm/Disarmarea(s).
Status Display Allowed
Whenanarea(s)ischosen,thefollowingdisplaysareallowed:
•ArmedStatusoftheselectedarea(s)
•ZoneAlarmsandtroublesforburglary(NT,DY,EX,A1,A2)typezonesassigned
totheselectedarea(s)
•LatetoClosestatusoftheselectedarea(s)
•ZoneStatus(normal/fault)ofzonesthatareassignedtotheselectedarea(s)
Options and Actions Not Affected
ThefollowingoptionsarenotaffectedbytheDisplayAreasoperation.TheUser
Code authority level controls access to these items.
•SensorResetMenu •OutputsOn/OffMenu •SystemStatusMenu
•SystemTest/PanicTest •UserProles •ForgiveAnti-Passback
•ServiceRequest •SetSystemTimeandDate
•FireDrill •DisplayEvents
•24-hourzonesdisplayatkeypadsbasedonStatusListprogrammingonly
Note:Acommonareaanditsoperationscannotbeassignedtoaspecickeypad.
DisplayAreasexample:WhenDevice1hasDisplayAreassetto3,5,and8,it
annunciates troubles and alarms only for zones assigned to those areas.
When
arming/disarmingfromDevice1,onlyareas3,5,and8maybearmed/disarmed,even
whentheUserProlehasauthoritytoarm/disarmothersystemareas.
Exception:DisarmingofotherareasnotselectedinDisplayAreascanbe
accomplished by presenting a card that has disarming authority and matching
proleareaswithareasassignedinDeviceAccessAreas.
6.10
STRIKE TIME: 5
Strike Time
This option displays if DOOR is selected as Device Type.
Enteradooraccesstime,between1and250seconds,duringwhichakeypadoraccess
control device relay is activated. Magnetic locks or electric door strikes are connected
to the relay and released for the length of the strike time. Default is 5 seconds.
Enter0(zero)toactivatethedevicerelaywithatoggleaction.Thisallowstheuser
to activate or deactivate the device relay each time a valid user code is entered.
The device relay is activated or deactivated until a user code is entered again.
Note:TheRequesttoExitdooraccesstimeofakeypadorModel733Wiegand
Interface Module is not affected by this selection. It remains at 5 seconds.
6.11
STRIKE DELAY: 0
Strike Delay
This option displays if DOOR is selected as Device Type.
Enterthenumberofminutes,0to9,todelayadoorstrikeafteravalidcodeisentered
or a card read occurs. When a valid code or card read or code is received, the activation
of the door strike is delayed for the number of minutes programmed. The standard door
strikemessageissenttotheCentralStationreceiverandloggedintheDisplayEventsat
the time of card read or code entry and is not delayed. During this delay, all subsequent
codes entered or cards presented to the reader for a door strike are ignored and no
recordoftheattemptisstored.Enter0(zero)todisable.Defaultis0(zero).
6.12
FIRE EXIT NO YES
Fire Exit Release
Select YES to allow the door access relay at this address to be released whenever
FirepanickeysarepressedoraFireorFireVerifyzonealarmisintheStatusList.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire
VerifyzonealarmsfromtheStatusList.SelectNO to not allow the door access
relay at this address to be released.
6.13
OUT GROUP NO YES
Output Group
Select YEStoallowtheoutputgroup(relays)assignedtotheuserproletoturnON
when the device relay is activated for the programmed strike time. This could be
used to operate an elevator control. Default is NO. See the User Proles section in
theAppendixofthisdocumentformoreinformationaboutproles.