XR100 Series Programming Guide Digital Monitoring Products
33
Output OptiOns
Output Options
11.1
OUTPUT OPTIONS
Output Options
This section allows you to program panel output options. The panel provides
twoFormCrelays(1and2)andfourswitchedground(opencollector)outputs
numbered3to6.UsetheJ22LX-Busonthepanelandmultiple716Output
ExpanderModulestosupportupto100additionalrelayoutputs.Alternately,when
using the 1100X wireless receiver, 45 wireless outputs are available. Refer to the
XR100SeriesInstallationGuide(LT-0899)forcompleteinformation.
Select from the following output numbers:
•1to6
•450to474—Slowresponsetime*wirelessoutputs(activateswithin15seconds)
•480to499—Fastresponsetime*wirelessoutputs(activateswithin1second)
•500to599—LX-Busoutput
•D1toD8—Keypaddoorstrikerelayforaddresses1-8
•G1toG20—Outputgroup
* The response time of a wireless output is the time it takes for a wireless output
to activate once the panel event occurs. You determine whether a wireless output
is a slow or fast response based on the output number assigned. A slow response
output number extends battery life, but response time may be up to 15 seconds.
A fast response output number responds within 1 second, but reduces battery life.
Refertothespecicwirelessoutputinstallationguidetodeterminebatterylife.
11.2.1
CO OUTS: - - - - - -
Cutoff Output
Outputs1to6canbeenteredheretoturnoffafteratimespeciedinCUTOFF
TIME.Todisablethisoption,pressanySelectkeytoclearthedisplaythenpress
COMMAND. The Cutoff Output displays dashes when no outputs are selected.
11.2.2
CUTOFF TIME: 0
Output Cutoff Time
IfaCutoffOutput(1-6)isassigned,enteraCutoffTimeof1to99minutesforthe
outputtoremainon.Enter0(zero)forcontinuousoutput.
11.3
COMM TRBL OUT: 0
Communication Trouble Output
EntertheoutputnumbertoturnonwhenaDDsystemfailstocommunicateon
three successive dial attempts or if the backup communication line transmits a
report.TheCommunicationTroubleOutputalsoturnsonwhenNETisselected
astheprimarycommunicationmethodandNETcommunicationfailsafterone
minute.WhenNETcommunicationisrestoredtheCommunicationTroubleOutput
automatically turns off.
To manually turn the output off, disarm any area or select Off for the output
numberintheUserMenuOutputsOn/Offsection.Enter0(zero)todisablethis
output.
11.4
FIRE ALR OUT: 0
Fire Alarm Output
Entertheoutputnumbertoturnonwhenaretypezoneisplacedinalarm.The
outputisturnedoffusingtheSensorResetoptionwhilenoadditionalretype
zonesareinalarm.Enter0(zero)todisable.Thisoutputisnotcompatiblewith
Cutoff Outputs.
11.5
FIRE TRB OUT: 0
Fire Trouble Output
Entertheoutputnumbertoturnonwhenaretypezoneisplacedintrouble,
when a supervisory type zone is placed in trouble, or when any system monitor
(AC,Battery,PhoneLine1orPhoneLine2)isplacedintrouble.Theoutputturns
offwhenallreandsupervisorytypezones,orsystemmonitorsarerestoredto
normal.Enter0(zero)todisablethisoutput.Thisoutputisnotcompatiblewith
CutoffOutputs.Thisoutputcanbeconnectedtoalamp,LED,orbuzzerusingthe
DMPModel716OutputExpansionModule.