XR500 Series Programming Guide Digital Monitoring Products
55
Zone InformatIon
19.12.4
NRM OPEN NO YES
Normally Open
Select NO if the contact connected to the wireless transmitter is Normally Closed.
19.12.5
NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - option to program a new zone. Select NO to
display the Alarm Action option.
19.13
ALARM ACTION . . . .
Alarm Action
This option allows you to change any Zone Type standard denitions. When the Zone Type
is specied, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a non-24-hour
zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is
always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following exceptions:
When a Fire Verify zone initiates an alarm, the panel performs a Sensor Reset. If any Fire
Verify zone initiates an alarm within 120 seconds after the reset, an alarm is indicated.
If an alarm is initiated after 120 seconds, the cycle is repeated and a zone fault report is
sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
19.14
DISARMED OPEN
Disarmed Open
Denes the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to dene: Report to transmit, Relay Output to
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press COMMAND to continue.
19.15
MSG: TROUBLE
Report to Transmit
Press any Select key to display the following report options: A, T, L, S, C, and - (dash).
A T L -
ALARM - Select A to send an alarm report to the receiver and activate the bell output
according to zone type. The zone name appears in the panel alarmed zones and status
lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name appears in
the panel alarmed zones and status lists.
Note: UL requirements prevent the Alarm (A) and Trouble (T) action for Fire (FI), and Fire
Verify (FV) zone types from being changed.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell output
activates and the zone name appears in the panel alarmed zones and status lists.
- (Dash) - When you select a – (dash), reports are NOT sent to the receiver. The bell
output does not activate and there is no display in the panel alarmed zones or status list.
Only the relay output selected in the next section operates.
D S C
DOOR PROPPED - Selecting D allows the following operation: The time programmed into
ENTRY DLY 4 in the System Option section begins to count without displaying on keypad.
If the time expires and the zone has not returned to normal, the keypad trouble buzzer
starts and CLOSE THE DOOR appears on the keypads programmed into the PREWARN
ADDRESS section. The time programmed into ENTRY DLY 4 begins to count down again
internally. If the time expires a second time and the zone has not returned to normal, a
fault report is sent to the receiver and the zone name - OPEN message displays on the
keypads until a code is entered. The bell output does not activate for the Door Propped
operation.
SILENCE/RESET - Select S when the zone (not FI, SV, or FV) is connected to a DMP Model
303 Silence/Reset switch, the zone can be used to silence the alarm bell and perform a
sensor reset without using a keypad. A report is NOT sent to the receiver except for the
bell silence report.
CANCEL AMBUSH - Select C for the zone to cancel the Early Morning Ambush timer and
stop an Ambush message from being sent to the receiver. Faulting the zone takes the
place of a second user code being entered at the keypad and is only available for non-re
type zones. Area assignment for the zone does not affect this option. See Early Morning
Ambush in Area Information programming .