Digital Monitoring Products, Inc.
1912XR Programming
Page 17
8.5C COMMUNICATION FAILURE OUTPUT - This output is turned on when any of
the following conditions occur:
a DD system fails to communicate on three successive dial attempts
a MPX system does not communicate with the receiver for 150 seconds or if
the backup communication module transmits a report
Enter zero to disable this output.
8.5D FIRE ALARM OUTPUT - This output is turned on any time a fire type loop is
placed in alarm. The output is turned off using the Sensor Reset option while no
additional fire type loops are in alarm. Enter zero to disable this output.
8.5E FIRE TROUBLE OUTPUT - This output is turned on any time a fire type loop is
placed in trouble or when a supervisory type loop is placed in alarm or trouble.
The output is turned off when all fire and supervisory type loops are restored to
normal. Enter zero to disable this output.
8.5F AMBUSH OUTPUT - This output is turned on any time an Ambush code is
entered at a keypad. The output is turned off using the Sensor Reset option.
Enter zero to disable this output.
8.5G ENTRY OUTPUT - This output is turned on at the start of the entry delay time.
The output is turned off when the area is disarmed or the entry delay time
expires. Enter zero to disable this output.
8.5H EXIT OUTPUT - This output is turned on any time an exit delay time starts in any
area of the system. The output is turned off when the area arms or when the
arming has been stopped. Enter zero to disable this output.
8.5I READY OUTPUT - This output is turned on whenever all disarmed burglary loop
types are in a normal state. The output is turned off when any disarmed burglary
type loop is in a bad state. Enter zero to disable this output.
8.5J PHONE TROUBLE OUTPUT - This output is turned on any time the phone line
monitor detects a voltage below 3 VDC. The output is turned off when phone
voltage rises above 3 VDC. Enter zero to disable this output.
8.5K LATE TO CLOSE OUTPUT - This output is turned on any time a programmed
area in a closed period remains disarmed. The output is turned off when the area
is armed, the closing is extended, or the schedule is changed.
8.5L DEVICE FAIL OUTPUT - This output is turned on any time an addressed device
fails to respond to polling from the panel. The output is turned off when the
device responds to polling or is removed from the system. Enter zero to disable
this output.
Any Output Option can be used with output numbers 1 through 6 and 100 through 199.
FIRE ALR OUT: 0
AMBUSH OUT: 0
ENTRY OUT: 0
READY OUT: 0
FIRE TRB OUT: 0
LATE CLS OUT: 0
PH TRBL OUT: 0
EXIT OUT: 0
COM FAIL OUT: 0
DVC FAIL OUT: 0
8-OUTPUT OPTIONS