30
InstallatIon
28.5 Proprietary Dialer
TheModelXR2500Fprovidesproprietaryservicewhenconguredasadigitaldialer.
28.6 DACT Central Station
DACTCentralStationservicecanbeprovidedunderbyaddinganAdemcoAB12Mbellandbellhousing.
28.7 Bell Cutoff
TheBellCutofftimecannotbelessthan15minutes.
28.8 Standard or Encrypted Line Security
StandardLineSecurityisprovidedwhenconguredasaPath1NETsystemusinganXR500Npanel.TheNET
Check-intimemustbesetto06minutesorRDM.WhenprogrammedforStandardLineSecurity,ExitTime
Restartisdisabled.Whenadialerisrequiredfor06minutecheck-intime,anattackresistantenclosure
(DMPModel350A)isrequired.Whenthecheck-intimeissettoanumberlessthan200seconds,anattack
resistant enclosure is not required.
ToprovideEncryptedLinesecurity,installanXR500Epanel.
ForEncryptedLinesecurityoperation,communicationbetweenthePremiseandSupervisingStationprovides
128bitencryptionwhenusinganXR500EpaneloranXR500panelwithaniCOM-EEncryptedNetworkAlarm
Router.
TheModelXR500SeriesProtectedPremisesControlUnitissuitableforStandardLineSecurityservicewhen
conguredforNETcommunicationwithSCS-1Rreceivingsystem.Thiscongurationisapprovedforthe
following:
AMCX-CentralStationAlarmUnits
APOU-ProprietaryAlarmUnits
28.9 Wireless Audible Annunciation Option
TheWirelessAudibleoptionmustbeselectedasANYforcommercialapplications.
28.10 Model 463G CELL Only, Standard or Encrypted Line Security
StandardorEncryptedLineSecurityisprovidedwhenprogrammedusingCELLwithnobackup.XR500
cellularcommunicationisusedasprimarywitha3minutecheck-inwhenarmedordisarmed.
Path 1 programming
CommType:=CELL Checkin:=3minute
Path Type: = Primary FailTime:=3minute
Encrypt:=NOorYES* TestRpt:=NO
SubCode:=NOorYES
*ForEncryptedLineSecurity,programaPassphraseinNetworkOptions.