InstallatIon
Listed Compliance Specications
24.1 Introduction
ForapplicationsthatmustconformtoalocalauthoritiesinstallationstandardoraNationalRecognizedTesting
Laboratorycerticatedsystem,pleaseseethefollowingsections.
Universal UL Burglary Specications
25.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theXR2500Fpanelinaccordancewithanyburglarystandards.Additionalspecicationsmayberequiredbya
particularstandard.SeetheXR500ProgrammingGuide(LT-0679).
25.2 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI/NFPA70,ANSI/UL681.Alltransformerwiresmustbe
installed in conduit.
25.3 Control Outside of Protected Area
APotterEVDorSentrol5402shouldbeusedinplaceofalinedcabinetwhenthepanelisinstalledoutside
oftheprotectedarea.Frontandreartamperswitchesarerequired.Refertothesystemwiringdiagram
andFigure2.
25.4 Police Station Phone Numbers
Thedigitaldialertelephonenumberprogrammedforcommunicationmustnotbeapolicestationphone
number.
25.5 Bypass Reports
TheBypassReportsoptionmustbeprogrammedasYESforalllistedburglaryapplications.
25.6 System Maintenance
Toensurecontinuoussatisfactoryoperationofanyalarmsystem,properinstallationandregular
maintenancebytheinstallingalarmcompanyandfrequenttestingbytheenduserisessential.Offeringa
maintenanceprogramandacquaintingtheuserwiththecorrectproceduresforsystemuseandtestingis
alsotheresponsibilityoftheinstallingalarmcompany.
25.7 Listed Receivers
OperationhasbeenveriedwiththeDMPSCS-1R,Sur-GardSG-HLR2-DG,FBIICP220PB,Osborne-Hoffman
Quick-Alert,andRadionicsD6500receivers.Itistheinstaller’sresponsibilitytoverifycompatibilitybetween
theXR2500Fandthereceiverusedduringinstallation.Theinstallershallverifythecompatibilityofthe
receiver and the system on a yearly basis.
25.8 Power Supply Supervision
Forcommercialburglaryapplicationsthepowersupplyforalllocalbellsshallbeunder24-hourprotection.
RefertotheSecondaryPowerSupplysectioninthisdocument.
25.9 Wireless Tamper
TheZoneInformationDisarmedOpenMessagetoTransmitmustbeprogrammedTrouble(T).(Notapplicable
toANSI/UL1023).
25.10 Wireless External Contact
Whenused,theExternalContactof1101or1102mustbeprogrammedNormallyClosed.
25.11 Wireless Supervision Time
TheZoneInformationSupervisionTimecannotbesetto0(zero).
25.12 Detect Wireless Jamming
TheDetectWirelessJammingoptionmustbeprogrammedYES.(NotapplicabletoANSI/UL1023).