XRSuper6/XR20/XR40 Programming Guide Digital Monitoring Products
19
ouTPuT oPTionS
Bell Options
7.1
BELL OPTIONS
Bell Options
This section allows you to program the panel bell output functions.
7.2
BELL CUTOFF: 5
Bell Cutoff Time
Enter the maximum time from 1 to 15 minutes the Bell Output remains on. If the
Bell Output is manually silenced or the system is disarmed, the cutoff time is reset.
Enter zero to provide continuous bell output. Default is 5.
Note: To support the Cancel/Verify operation on an All/Perimeter or Home/Sleep/
Away system, set the Bell Cutoff Time to greater than 0.
Note: For ANSI/SIA CP-01 UL installations, the Bell Cutoff Time must be set to a
minimum of six (6) minutes.
7.3
BELL TEST NO YES
Automatic Bell Test
When YES is selected, the Bell Output is turned on for two seconds when all areas
in the system are armed. The Bell Test only occurs when the areas are armed from
a keypad. Arming performed from an Arming zone or remotely from Remote Link™
does not activate the Bell Test. In addition, the Closing Wait feature is activated if
Opening/Closing Reports is YES. See OPENING/CLOSING AND USER REPORTS.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the
panel receives an acknowledgment of the closing report from the central station
receiver. During the delay, the keypad displays DIALING . . . Once the closing
is acknowledged, the keypad buzzes for one second and then displays the armed
message.
7.4
BELL OUTPUT:
Bell Output
Enter the output number when needed to follow the panel Bell Output operation for
all action and off conditions. Enter 0 (zero) to disable.
Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action is
pulse.
7.5
BELL ACTION . . .
Bell Action
This denes the type of Bell Output for zone alarms. Trouble conditions do not
activate the Bell Output. There are seven zone types you can program individually
for Bell Output. To provide a steady Bell Output, enter S. For a pulsed output,
enter P. For a Temporal Code 3 output, enter T and for no Bell Output, enter N.
7.5.1
FIRE TYPE: P
Fire
Denes Bell Action for Fire Type Zones. The default is set at P.
7.5.2
BURG TYPE: S
Burglary
Denes Bell Action for Burglary Type Zones. The default is set at S.
7.5.3
SUPRVSRY TYPE: N
Supervisory
Denes Bell Action for Supervisory Type Zones. The default is set at N.
7.5.4
PANIC TYPE: N
Panic
Denes Bell Action for Panic Type Zones. The default is set at N.
7.5.5
EMERGNCY TYPE: N
Emergency
Denes Bell Action for Emergency Type Zones. The default is set at N.
7.5.6
AUXLRY 1 TYPE: N
Auxiliary 1
Denes Bell Action for Auxiliary 1 Type Zones. The default is set at N.
Note: For ANSI/SIA CP-01 UL installations, a bell action must be programmed.
7.5.7
AUXLRY 2 TYPE: N
Auxiliary 2
Denes Bell Action for Auxiliary 2 Type Zones. The default is set at N.
Note: For ANSI/SIA CP-01 UL installations, a bell action must be programmed.